48 ECOM0010 - User manual
6.2 Manual tuning
Set 2 in parameter 5 (
7XQH
word 2005).
The manual procedure allows the user a greater exibility on
deciding when to update PID algorithm parameters.
This procedure is activated writing 1 in the word modbus
1004.
The reference threshold to calculate the new PID parameters
is given by the result of the following operation:
Tuning threshold = Setpoint (word 1001) Par.6
VGWX
(word 2006)
Ex.: if setpoint is 100.0°C and Par.6
VGWX
is 20.0°C, the
threshold to calculate PID parameters is (100.020.0) = 80.0°C.
N.B.: for greater accuracy in the calculation of PID parameters
it is recommended to launch the manual tuning when the
process is far from setpoint.
6.3 Synchronised tuning
4FUJOQBSBNFUFS
7XQH
word 2005).
This procedure has been designed to calculate correct PID
values on multi-zone systems, where each temperature
is inuenced by the next zones. Writing in word 1004, the
device works as follows:
Word 1004 value Action
Tune o.
Control output OFF
Control output ON
Tuning active
Tuning completed: control output OFF
The operation of this Tuning mode is the following: the
master switches o or turns on all controllers (value 1 or 2 on
word 1004) for a time which is long enough to create inertia